Wallace & Tiernan Acutec 35 Gas Detection System utilizes the latest on-line gas monitoring technology to provide a flexible and reliable, self testing detection system in a compact modular design.


leak



Operating Ranges

Gas

Standard Range (ppm)

Min. Range (ppm)

Max. Range (ppm)

Ammonia

0-100

0-50

0-500

Chlorine

0-10

0-5

0-50

Sulfur Dioxide

0-20

0-10

0-100

Sensor/Transmitter A highly efficient electrochemical gas sensor for location in areas where gas leakage could occur is combined with an equally efficient transmitter, both housed in a NEMA 4x enclosure. Digitally convereted measuresments of gas concentrations are then sent to the Receiver Module located anywhere up to 1000 feet away.
Battery back-up System
the Battery back-up option consists of a sealed lead-acid battery mounted in its own enclosure. In the evet of a power failure, it will maintain all Receiver functions for a minimum of 12 hours on a dual point system. Battery charging is fully automatic and continuous through the Power Supply Module.